Balonne Emergency Mobile Generators

Tender ID: 626914


Tender Details

Organisation:
Tender #:
BSC 26/27 - T06  
Status:
Closed
Publish Date:
28 September 2026
Closing Date:
28 October 2026
Closing Time:
03:00 PM (Australia/Queensland)

Tender Description

⁠⁠⁠Overview

Balonne Shire Council invites tenders from suitably qualified tenderers for the supply and delivery of four trailer mounted diesel generators. The generators will be utilised for emergency power supply to critical Council infrastructure, including water, sewerage, disaster management facilities and community assets.

Scope

The scope includes the supply and delivery of:

  • One (1) trailer mounted diesel generator, approximately 145kVA standby capacity
  • Three (3) trailer mounted diesel generators, approximately 45kVA standby capacity

Large Generator

  • One (1) trailer mounted generator
  • Standby rating: minimum 145kVA
  • Prime rating: minimum 135kVA

Small Generators

  • Three (3) trailer mounted generators
  • Standby rating: minimum 45kVA
  • Prime rating: to manufacturer's standard

Engine

  • Diesel

Alternator

  • Brushless
  • Include AVR voltage regulation
  • Have Class H insulation

Output

  • 415 Volt three phase output
  • 240 Volt single phase output
  • 50Hz frequency
  • Overload protection
  • Earth fault protection
  • Emergency stop system

Fuel System, 145kVA Unit

  • Minimum 800 litre integrated fuel tank
  • Fuel tank to be bunded
  • Minimum 24-hour operation at 75% load
  • External fuel connection point for extended operation

Fuel System, 45kVA Units

  • Minimum 200 litre integrated fuel tank
  • Fuel tank to be bunded
  • Minimum 12-hour runtime at 75% load

Canopy

  • Fully weatherproof and lockable
  • Corrosion resistant and of powder-coated or galvanised steel construction
  • Fitted with lifting points

Control System

  • Digital controller
  • Engine protection monitoring
  • Battery voltage monitoring
  • Fuel level monitoring
  • Run hours display
  • Fault display
  • Auto start capability

Electrical Connection

  • Main circuit breaker
  • RCD protection where applicable
  • IP-rated outlets
  • Generator operating instructions mounted within canopy
  • Connection as per 2685-ELEC-1 rev0 Generator Change Over Switch

Accessories

  • Battery isolator
  • Emergency stop button
  • Fire extinguisher mounted to trailer
  • Reflective safety signage
  • Lockable document holder
  • 25m connection lead

Information Requested

Tenderers are to nominate all outlet configurations and identify the following in their response:

  • Outlet sizes
  • Outlet quantities
  • Connection arrangements

Instructions to Tenderers

Suppliers are advised to familiarise themselves with the specification, particularly the commissioning, training and documentation requirements.